Free-Cooling Chiller
- Oil-Free Magnetic-Bearing Technology
Oil-free, variable-speed magnetic-bearing centrifugal compressors reduce mechanical friction and adjust operation to changing loads, supporting efficient part-load performance.
- Integrated Free Cooling
Free-cooling coils are integrated into the condenser module. When outdoor temperatures are suitable, ambient cooling reduces the demand on the mechanical refrigeration system.
- Efficient Heat Transfer and Variable-Flow Operation
An efficient evaporator, finned-coil condenser, and EC fans work together to support efficient cooling. Variable-flow operation can reduce pumping energy at part load when coordinated with the system pumps.
- Multiple Independent Refrigerant Circuits
Multiple independent refrigerant circuits help limit the impact of a single-circuit failure. Redundant capacity is configured and verified against project loads and cooling-continuity requirements.
Cooling Plant Equipment for Critical IT Environments
Chillers can be configured around changing data center loads, year-round operating requirements, and redundancy targets to support different project scales and development phases.

Cooling plant selection matched to the water-system requirements of high-density computing facilities.

Chiller configurations matched to project loads and cooling-continuity requirements.

Capacity planning aligned with initial loads and future expansion.

Efficiency and free-cooling opportunities assessed against the existing water system.
Selection and Configuration Support for GEAREA Magnetic-Bearing Chillers
Compressor combinations, heat exchangers, and fan configurations are selected to match project cooling loads, entering and leaving fluid temperatures, fluid properties, ambient conditions, efficiency targets, and redundancy requirements.


Flexible Electrical and Control Options
Options include dual power inputs, automatic transfer switches (ATS), power-factor correction capacitors, and ultracapacitors. The electrical arrangement should be confirmed against site power conditions and cooling-continuity requirements.
Water-System Integration
Selection considers water or glycol-based fluids, design flow, allowable pressure drop, and temperature requirements. Variable-flow operation should be coordinated with the system pumps and controls.

More About Free-Cooling Chiller
- Data Sheet
| R1234ze | Free-Cooling Chiller | GMAC250 | GMAC400 | GMAC500 | GMAC650 | GMAC800 | GMAC950 | GMAC1200 | GMAC1400 |
| Outdoor Air: 95°F Fluid: 30% EG EWT/LWT: 78.8°F / 68°F | Nominal cooling capacity (tons) | 94 | 128 | 171 | 199 | 242 | 270 | 370 | 398 |
| EER (Btu/Wh) | 15.9 | 15.8 | 15.7 | 15.6 | 15.3 | 16.2 | 15.0 | 15.0 | |
| Power Input (kW) | 101 | 138 | 177 | 212 | 261 | 278 | 424 | 471 | |
| (ZET), °F | 47 | 47 | 50 | 50 | 50 | 51 | 50 | 48 | |
| Components | No. of Compressors | 2 | 2 | 3 | 3 | 3 | 3 | 4 | 4 |
| No. of Refrigerant Circuits | 2 | 2 | 3 | 3 | 3 | 3 | 4 | 4 | |
| Power Supply | 460 V / 3 Ph / 60 Hz | ||||||||
| Fans | 6 | 8 | 12 | 14 | 16 | 20 | 22 | 22 | |
| Evaporator | Shell-and-Tube | ||||||||
| Condenser | Finned Coil | ||||||||
| Free-Cooling | Free-Cooling Coil | ||||||||
| Dimensions | Length (in.) | 136.2 | 177.6 | 260.2 | 301.6 | 342.9 | 425.6 | 466.9 | 466.9 |
| Width (in.) | 88.6 | 88.6 | 88.6 | 88.6 | 88.6 | 88.6 | 88.6 | 88.6 | |
| Height (in.) | 109.8 | 109.8 | 109.8 | 109.8 | 109.8 | 109.8 | 109.8 | 109.8 | |