Dry Coolers
- Free Cooling for Lower System Energy Ues
When outdoor temperatures are suitable, ambient air removes heat from the circulating fluid. Integration with higher-temperature water systems can extend free-cooling availability and reduce chiller runtime.
- Designed for High-Temperature, High-ΔT Water Loops
Units are selected for data center water loops with elevated operating temperatures and large temperature differences, taking into account entering and leaving fluid temperatures, fluid type, design flow, and outdoor conditions.
- Variable-Speed EC Fans
Fan speed adjusts to ambient conditions and heat-rejection demand. At lower loads or outdoor temperatures, reduced fan speeds help lower auxiliary power consumption while maintaining stable heat rejection.
- Optional Adiabatic Pre-Cooling
Under favorable wet-bulb conditions, the optional pre-cooling section lowers the air temperature entering the coil. Controlled water use helps balance heat-rejection performance, operating efficiency, and water consumption.
Heat Rejection for Different Data Center Projects
Dry coolers can be selected around water-loop temperatures, project loads, local climate, and construction phases to provide outdoor heat rejection for data centers of different sizes.

Multiple-unit arrangements matched to the overall heat-rejection load.

Heat-rejection capacity deployed in stages as the facility expands.

Higher operating fluid temperatures create more opportunities for free cooling.

Free-cooling integration assessed against existing water-system conditions.
Selection and Configuration Support for GEAREA Dry Coolers
Selection considers the heat-rejection load, fluid type and concentration, entering and leaving fluid temperatures, outdoor design conditions, and available space to match unit capacity, fan quantity, and water-system connection requirements.


Available Options
Available options include adiabatic pre-cooling, corrosion-resistant coil coatings, automatic coil cleaning, air-inlet screens or filters, water softening, UV sterilization devices, and independent control panels. Availability and suitability are confirmed in the project-specific technical proposal.
Installation and Operating Requirements
Selection and layout should account for airflow clearance, hot-air recirculation between adjacent units, coil removal, control-panel access, lifting, and piping stress relief. Final performance and dimensions are subject to GEAREA selection software and approved technical submittals.

More About Dry Cooler
- Data Sheet
| Parameter | Unit | GRDC-F130H-NA | GRDC-F260H-NA | GRDC-F390H-NA | GRDC-F520H-NA |
| Heat Rejection Capacity | tons | 37.0 | 73.9 | 110.9 | 147.9 |
| Airflow | cfm | 25,427 | 50,853 | 76,280 | 101,706 |
| Number of EC Fans | — | 2 | 4 | 6 | 8 |
| Fan Input Power | hp | 5.1 | 10.2 | 15.3 | 20.4 |
| Power Supply | — | 460–480 V / 3 Ph / 60 Hz | |||
| Fluid Flow | gpm | 32.6 | 65.6 | 98.2 | 131.2 |
| Fluid-Side Pressure Drop | psi | 6.1 | 6.7 | 7.4 | 8.0 |
| Sound Pressure Level | dB(A) | 72 | 73 | 73 | 74 |
| Net Weight | lb | 904 | 1,676 | 2,447 | 3,219 |
| Parameter | Unit | GRDC-F650H-NA | GRDC-F780H-NA | GRDC-F1040H-NA | GRDC-F1430H-NA |
| Heat Rejection Capacity | tons | 184.8 | 221.8 | 295.7 | 406.6 |
| Airflow | cfm | 127,133 | 152,559 | 203,412 | 279,692 |
| Number of EC Fans | — | 10 | 12 | 16 | 22 |
| Fan Input Power | hp | 25.5 | 30.6 | 40.8 | 56.1 |
| Power Supply | — | 460–480 V / 3 Ph / 60 Hz | |||
| Fluid Flow | gpm | 163.8 | 196.4 | 262.0 | 360.2 |
| Fluid-Side Pressure Drop | psi | 8.6 | 9.1 | 10.2 | 11.5 |
| Sound Pressure Level | dB(A) | 74 | 75 | 75 | 76 |
| Net Weight | lb | 3,990 | 4,762 | 6,305 | 8,620 |