Fan Wall Units
- High Airflow in a Compact Design
Chilled-water coils, filters, and fan arrays are integrated into a compact unit that can be configured around data hall layouts and service galleries.
- Independent EC Fan Speed Control
Each EC fan supports independent variable-speed control, allowing operation to be adjusted to airflow demand while helping reduce fan energy consumption.
- Configurable N+1 Fan Redundancy
Fan configurations are selected against project airflow, static pressure, and redundancy requirements. Performance after a single-fan failure is verified to help limit its impact on air delivery.
- Factory Assembly for Easier Installation and Service
Coils, filters, fans, and controls are assembled and tested at the factory to reduce on-site assembly. Service-side access and modular components simplify inspection, fault isolation, and replacement.
Air-Side Cooling for AI and Hybrid-Cooled Data Centers
GEAREA fan wall units can be selected around data hall airflow, chilled-water conditions, air-side cooling loads, and redundancy requirements to suit different data center layouts.

Air-side cooling matched to high-density computing environments.

Airflow and redundancy configured around data hall layouts and operating requirements.

Modular fan configurations support phased development requirements.

Removes heat from equipment that continues to rely on air cooling.
Selection and Configuration Support for GEAREA Fan Wall Units
Coils, fan quantities, and controls are selected around air-side cooling loads, airflow, external static pressure, entering-air conditions, and chilled-water parameters, with installation routes and service space also considered.


Airflow and Redundancy Configuration
Fan arrangements and redundancy are verified at the design duty point. An N+1 configuration requires confirmation that the remaining fans can meet the required airflow and static pressure with one fan unavailable.
Filtration, Valve, and Electrical Options
Filter options include 2-inch or 4-inch depths and MERV 8 or MERV 11 ratings. EPIV or two-way CCV valve options, harmonic mitigation filters, and electrical and control configurations can be selected to suit project requirements.

More About Fan Wall Unit
- Data Sheet
| Model | Airflow (CFM) | Nominal Cooling Capacity (TR) | Dimensions (L × W × H), in |
| GRAL017-FW | 17,000 | 31.3 | 96.5 × 72.8 × 54.3 |
| GRAL033-FW | 33,000 | 62.6 | 96.5 × 120.0 × 54.3 |
| GRAL049-FW | 49,000 | 93.8 | 144.5 × 120.0 × 54.3 |