x
Send Your Inquiry Today
Quick Quote
Cleanroom Air Handling Units Manufacturer in China

Cleanroom Air Handling Unit
Manufacturer in China

GEAREA cleanroom air handling units are built for flexibility and high standards in demanding industrial environments. Inside, modular functional sections can be freely configured to match your process needs, while maintaining precise control of temperature and humidity.

  • GRA Cleanroom Air Handling Units1
  • GRA Cleanroom Air Handling Units2
  • GRA Cleanroom Air Handling Units3
  • GRA Cleanroom Air Handling Units4
  • GRA Cleanroom Air Handling Units5
  • GRA Cleanroom Air Handling Units1
  • GRA Cleanroom Air Handling Units2
  • GRA Cleanroom Air Handling Units3
  • GRA Cleanroom Air Handling Units4
  • GRA Cleanroom Air Handling Units5
GRA Series

Cleanroom Air Handling Unit (Modular Type)

  • Wide airflow range: each unit handles 2,000–20,000 m³/h, suitable for different air-handling application sizes.
  • Customized design: mixing, pre-filtration, cooling, heating, humidification, fan, silencer, and heat-recovery sections can form different combinations to create HVAC solutions tailored to your project requirements.
  • High-efficiency smog & pathogen filtration: air filtration system consisting of primary filter, medium filter, and sub-HEPA filter allows for 99.9% pathogen & smog filtration.
  • Easy operation: smart control UI for one-step temperature & humidity setting, eliminating redundancy and error risks.

Why Choose GEAREA Cleanroom Air Handling Unit

GEAREA cleanroom air handling unit delivers ultra-quiet, energy-efficient HVAC systems that can reach desert-level dryness with patented technologies.

Noise Reduction
Noise Reduction

With GEAREA’s distributed damping vibration and noise control technology, the unit operates as quietly as 65 dB(A), creating a more comfortable acoustic environment.

Precise Environment Control
Precise Environment Control

The built-in refrigeration cycle with condensing heat redistribution device precisely regulates heat and humidity of supply air, ensuring reliable environment control.

Variable Humidity Options
Desert-Level Dryness

GEAREA advanced deep dehumidification technology delivers ultra-dry air with extremely low moisture content down to 8 g/kg (dry air).

Desert-Level Dryness
Energy Efficiency

Operations of DC inverter compressor and EC fans varies with conditions, achieving 40-50% energy reduction compared with conventional systems.

GEAREA Engineering Strength in Cleanroom Air Handling Unit

GEAREA cleanroom air handling units are built for owners who care about long-term reliability and energy bills. Each casing is tested to EN 1886, achieving D1 casing strength, L1 casing leakage, and F9 filter bypass leakage, meaning a robust, tightly sealed structure with minimal air and pressure loss in your system. Together with T2 thermal transmittance and TB2 thermal bridge levels, this reduces casing heat loss, lowers condensation risk around the unit, and delivers a cleaner, more efficient installation in demanding cleanroom and industrial applications, which translates into steadier conditions, better protection for your process, and an HVAC system that runs more efficiently, with fewer issues and lower lifetime operating costs.

GEAREA Engineering Strength in Cleanroom Air Handling Units

More About Cleanroom Air Handling Unit

Chilled Water Coil Performance TableInlet Air Dry-Bulb Temperature: 27°C
Inlet Air Wet-Bulb Temperature: 19.5°C
Water Inlet/Outlet Temperature: 7/12°C
Coil Face Velocity: 2.5 m/s
GR-Rated Airflow4-row6-row8-row
m³/hm³/sTotal Cooling Capacity
kW
Sensible Cooling Capacity
kW
Water Flow Rate
l/s
Water Pressure Drop
kPa
Total Cooling Capacity
kW
Sensible Cooling Capacity
kW
Water Flow Rate
l/s
Water Pressure Drop
kPa
Total Cooling Capacity
kW
Sensible Cooling Capacity
kW
Water Flow Rate
l/s
Water Pressure Drop
kPa
0220000.61280.6816100.71117110.812
0330000.818120.9823151.11126161.212
0440001.124161.21331201.51734221.619
0550001.431201.52039251.92743272.030
0660001.737251.81847302.22551332.428
0770001.943292.02055362.62660382.829
0880002.249332.32062413.02868443.331
0990002.555372.62170463.42977493.732
10100002.861412.92078513.72785544.113
12120003.373493.52194614.529102654.914
14140003.985574.128109715.216119765.718
16160004.498654.730125816.017136876.519
18180005.0110745.215140916.720153987.322
20200005.6122825.8171561017.5231701098.126
25250006.91531027.3171951279.32321313610.126
30300008.31831238.71723415211.22325516312.226
35350009.721414310.21927317813.02529819014.228
404000011.124416411.72331220314.93134021816.215
454500012.527518413.12335122816.81938324518.315
505000013.930520414.62539025418.62142527220.316
606000016.736624517.53246830422.32651032624.320
707000019.442728620.41454635526.12859538128.422
808000022.248832723.31762440629.83368043532.526
909000025.054936826.22070245633.53876549036.530
10010000027.861040929.12178050737.24085054440.631
12012000033.373249034.92693660844.735102065348.739
14014000038.985457240.827109271052.137119076256.841
16016000044.497665446.632124881159.644136087064.921
18018000050.0109873652.429140491367.039153097973.018
20020000055.6122081758.2331560101474.5441700108881.121

Chilled Water Coil Performance TableInlet Air Dry-Bulb Temperature: 34°C
Inlet Air Wet-Bulb Temperature: 28°C
Water Inlet/Outlet Temperature: 7/12°C
Coil Face Velocity: 2.5 m/s
GR-Rated Airflow4-row6-row8-row
m³/hm³/sTotal Cooling Capacity
kW
Sensible Cooling Capacity
kW
Water Flow Rate
l/s
Water Pressure Drop
kPa
Total Cooling Capacity
kW
Sensible Cooling Capacity
kW
Water Flow Rate
l/s
Water Pressure Drop
kPa
Total Cooling Capacity
kW
Sensible Cooling Capacity
kW
Water Flow Rate
l/s
Water Pressure Drop
kPa
0220000.622101.11628111.42231121.525
0330000.833141.61642172.02246192.225
0440001.144192.12757232.73662253.040
0550001.455242.61871283.42477313.727
0660001.766293.11685344.12292374.425
0770001.977333.71799404.724108435.226
0880002.287384.218113455.425123495.927
0990002.598434.719127516.126139556.628
10100002.8109485.218141576.824154627.427
12120003.3131576.319170688.126185748.928
14140003.9153677.324198799.5332168610.337
16160004.4175768.4272269110.8362469911.840
18180005.0197869.43125510212.24227711111.840
20200005.62199610.53528311313.54830812314.823
25250006.927311913.13535414116.92938515418.423
30300008.332814315.73542417020.32946218522.123
35350009.738316718.33849519823.73253921625.825
404000011.143719120.94756622627.13961624629.531
454500012.549221523.64863625530.54069327733.231
505000013.954723926.22270728333.91877030836.934
606000016.765628731.42884833940.62392437044.318
707000019.476533736.63099039647.425107843151.619
808000022.287438241.935113145354.229123249359.023
909000025.098443047.140127350960.934138655466.426
10010000027.8109347852.443141456667.736154061673.828
12012000033.3131257362.823169767981.344184873988.535
14014000038.9153066973.324198079294.8472156862103.337
16016000044.4174976483.8282262905108.4552464986118.043
18018000050.0196786094.22525451018121.94927721109132.838
20020000055.62186955104.72928281131135.45630801232147.544

Get a Fast Quote for Energy-Saving Cleanroom HVAC System

GEAREA designs and manufactures precision temperature and humidity control systems for factories and clean environments. We offer customized solutions that effectively reduce operating costs—typically saving up to 40% on electricity consumption. Please tell us your needs, and we will provide you with the best configuration and budget quote.
Scroll to Top