Steam Generation Heat Pump
- Flexible site selection: only needs outdoor installation space (roof, yard, platform); suitable for scattered factories and standalone workshops.
- Suitable for precision-critical industries: advanced vibration reduction minimizes interference with sensitive processes.
- Flexible steam output: offering two steam outlet options (120°C / 0.2 MPa and 140°C / 0.4 MPa) and a wide capacity range from 100 kg/h to 1000 kg/h.
Why Choose GEAREA Air-Source Heat Pump Generator?
GEAREA steam generation heat pump focuses on quiet operation, flexible installation, energy efficiency, and simple smart control.

GEAREA steam generation heat pump applies spring isolators, rubber pads, and flexible connectors to minimize noise and vibration, delivering smooth operation.

GEAREA steam generation heat pump features a small outdoor footprint and installation method similar to an AC outdoor unit, making it easy to deploy in existing sites.

GEAREA steam generation heat pump delivers about 30–50% energy reduction compared with traditional electric steam boilers, lowering operating costs.

Equipped with an intuitive UI and smart control, GEAREA steam generation heat pump enables users to start, monitor, and adjust the system easily in daily operation.
Reliable Installation for GEAREA Steam Generation Heat Pump
For reliable installation of the GEAREA Steam Generation Heat Pump, ensure the unit is placed on a professionally built concrete or steel foundation capable of supporting its operating weight. Keep the area clear of fire hazards, corrosive gases, and exhaust fumes, and avoid installing the unit under windows or between buildings. With proper clearances for air intake and maintenance, the system can run at peak performance. Expert electrical and piping work further ensures safety, efficiency, and long-term reliability—giving you confidence in every operation of your GEAREA Steam Generation Heat Pump.

More About Steam Generation Heat Pump
- Data Sheet
| Model | GHB-AS-28- 140/0.4-M | GHB-AS-37- 140/0.4-M | GHB-AS-42- 140/0.4-M | GHB-AS-55- 140/0.4-M | GHB-AS-72- 140/0.4-M | GHB-AS-88- 140/0.4-M | ||
| Electrical Protection Class | Class I | Class I | Class I | Class I | Class I | Class I | ||
| Ingress Protection Rating (IP Rating) | IPX4 | IPX4 | IPX4 | IPX4 | IPX4 | IPX4 | ||
| Operating Condition:20°C/15℃ Steam Temperature:140℃ | Rated Heating Capacity | kW | 21.04 | 27.51 | 31.61 | 41.23 | 53.84 | 66.26 |
| Rated Power Input | kW | 17.03 | 22.79 | 25.5 | 33.37 | 43.63 | 54.81 | |
| Rated Current | A | 32.3 | 43.3 | 48.4 | 63.4 | 82.9 | 104.1 | |
| COP | 1.24 | 1.21 | 1.24 | 1.24 | 1.23 | 1.21 | ||
| Steam Output Capacity | kg/h | 28 | 37 | 42 | 55 | 72 | 88 | |
| Steam Temperature Range | ℃ | 130-140 | 130-140 | 130-140 | 130~140 | 130~140 | 130~140 | |
| Power Supply | 380V | 380V | 380V 3N~50Hz | 380V | 380V | 380V | ||
| Refrigerant | Low-Temperature Stage | R410a | R410a | R410a | R410a | R410a | R410a | |
| High-Temperature Stage | R1233zd | R1233zd | R1233zd | R1233zd | R1233zd | R1233zd | ||
| Water-Side Heat Exchanger | Rated Water Flow Rate | m³/h | 3.6 | 4.7 | 5.4 | 7.1 | 9.3 | 11.4 |
| Water-Side Pressure Drop | kPa | 35 | 35 | 45 | 45 | 50 | 50 | |
| Make-up Water Connection Size | DN | DN20 | DN20 | DN20 | DN20 | DN20 | DN20 | |
| Drain Connection Size (Soft Water Tank) | DN | DN20 | DN20 | DN20 | DN20 | DN20 | DN20 | |
| Blowdown Connection Size (High-Temperature Water) | DN | DN20 | DN20 | DN20 | DN20 | DN20 | DN20 | |
| Overall Dimensions | L × W × H | mm | 1600*960*1300 | 1600*960*1300 | 1600*960*1300 | 1960*960*2110 | 1960*960*2110 | 1960*960*2110 |
| Sound Pressure Level | dB(A) | ≤65 | ≤65 | ≤70 | ≤70 | ≤72 | ≤75 | |
| Weight | kg | 400 | 500 | 600 | 700 | 900 | 1200 | |